Circular ceiling diffuser with discs for supply air.

Circular supply air diffusers with adjustable discs for ceiling installation. The air diffuser is well suited for constant as well as variable airflow. Air above or below room temperature can be discharged in a horizontal or vertical spread pattern into the room. The disc technique allows the supply of air substantially below room air temperature. It is possible to change the spread pattern after commissioning without altering the airflow, pressure drop or sound level.

  • Adjustable discs, 360°
  • 100% flexible spread pattern
  • Can be used for vertical air diffusion
  • Simultaneous horizontal/vertical air diffusion is possible
  • Swirl function
  • Substantial induction capacity
  • Can be used with ALS commissioning box
  • Available in a galvanized version
  • Standard colour White RAL 9003
    • 5 alternative standard colours
    • Other colours upon request
 

EAGLE Single
EAGLE Single
Product view
 
Discs
Discs
Close-up of disc for easy adjustment of sp…


AIR FLOW - SOUND PRESSURE ROOM (Lp10A) *)

EAGLE Single

ALS

l/s

Size

Size

25 dB(A)

30 dB(A)

35 dB(A)

125

100-125

24 (34)

29 (40)

36 (47)

160

125-160

37 (50)

45 (58)

55 (70)

200

160-200

54 (78)

70 (92)

85 (108)

250

200-250

84 (105)

101 (122)

124 (142)

315

250-315

120 (143)

145 (168)

170 (200)

400

315-400

180 (230)

220 (265)

265 (310)

The data for the air diffuser + commissioning box is specified for 50 Pa total pressure. The data for the air diffuser alone is in brackets.

*) Lp10A = Sound pressure incl. A-filter with 4 dB room attenuation and 10 m2
room absorption area
*) Lp10A = Sound pressure incl. A-filter with 4 dB room attenuation and 10 m2room absorption area.

Downloads


3 Hits   Page < 1 >

   

 



Article Name Type Size Date Add to bucket
Page < 1 >
EAGLE Single  Building product declaration Declarations 42.15kB 4/8/2014 Add to bucket
EAGLE Single  Exposed circular ceiling terminal with discs Catalogue/Product sheets 1.04MB 10/10/2018 Add to bucket
EAGLE Single  Installation - Commissioning - Maintenance Instructions/Manuals 971.89kB 3/17/2016 Add to bucket