The combination of a GOLD with Smart Link DX and Epsilon Sky Chiller/heat pump is a seamless, integrated and sustainable solution that secures system functionality in all conditions.

Main functionality

The SMART Link DX and Epsilon Sky function for GOLD regulates the supply air temperature of the GOLD RX unit, providing cooling or heating while managing one or two EPSILON Sky reversible heat pumps. A key benefit is its easy connection, requiring only one Modbus cable between GOLD and EPSILON Sky.

Added value

All control, activation, and alarms are integrated into GOLD’s IQ-logic and IQ-Navigator. The system ensures minimum airflow for safe operation, uses the rotary heat exchanger to compensate during defrost or oil recovery, and enhances sustainability with R32 refrigerant. Multiple heat pumps offer better compliance with EN-378-1 standards, sequential defrosting, and staggered start-ups for efficient performance.

How it works

The flow chart above shows the schematics of the SmartLink DX and EPSILON Sky function. A couple of things to consider:

  1. GOLD controls one or two EPSILON Sky in sequence to keep required supply air temperature
  2. A neutral zone can be set when unit is not operating
  3. Regulation can be based on room temperature, extract air temperature, or outdoor air related extract air tempature
  4. If more than one EPSILON Sky is connected to the GOLD, functions like sectional de-frosting, and unit with lowest running time will start first are available
  5. All units in operation are working with the same power (parallel)
  6. When selecting a reversible heatpump solution, two EPSILON Sky is recommended, to be able to have a lower minimum airflow during defrost cycle.

Technical details

  • In GOLD, when selecting SMART Link DX function, the control system automatically activates the extra regulation sequence
  • GOLD controls the heat pump, to keep either supply air temp, room air temp or extract air temp at set point. Neutral zone function is used to set start limits for cooling and heating
  • Additional functions can be used to influence the supply air temp set point: Extract air compensation, Outdoor air related extract air compensation & summer night cooling
  • When combining this solution with a VAV/DCV system (pressure-controlled GOLD), minimum airflow demand for the chiller/heatpump to work properly must be respected (see manual below).

Read more: